Transient ground voltage + ultrasonic sensor

Products > Sensor series > Transient ground voltage + ultrasonic sensor

Transient ground voltage + ultrasonic sensor

Transient ground voltage + ultrasonic partial discharge sensor is composed of communication module, main processor and sensor. The communication module is responsible for data communication with the aggregation node, and the main processor controls the sending and receiving of data through the serial port protocol. The sensor is responsible for collecting PD data, and the main processor processes, analyzes and sends the collected data.

Serial number

Parameter name

Standard parameter values

1

Working power

Lithium battery

2

Letter of agreement

Adopt LoRa-based 470MHz frequency band wireless communication, in line with Q/GDW12020 requirements

3

Protection class

Not lower than IP40

4

TEV detection band

10MHz-50MHz

5

TEV accuracy

±1dB

6

Ultrasonic detection frequency band

38kHz-42kHz

7

Ultrasonic accuracy

±1dB

8

Use period

≥5 years

9

Installation method

Magnetic adsorption

10

Wireless transmission distance

more than 50 meters

11

Data upload cycle

The factory configuration is 1 time/1 minute, and the reporting period can be configured online.

12

Size

140mm(L)*85mm(W)*32.5mm(H)